- Basic Design principles: – Structural steel shall be designed in accordance with the ‘General Construction in steel Code of Practice (IS 800 LSD).
- Load Combination
1. 1.5 D.L. + 1.5 C.L.
2. 1.5 D.L. + 1.0 DYNAMIC
3. 1.5 D.L. + 1.0 DYNAMIC + 1.0 EQX
4. 1.5 D.L. + 1.0 DYNAMIC + 1.0 EQZ
5. 1.0 D.L +1.0 WLX
6. 1.0 D.L +1.0 WLZ
7. 1.0 D.L +1.0 WLX + 1.0 CL
8. 1.0 D.L +1.0 WLZ + 1.0 CL
Where,
D.L. = Dead Load
C.L. = Cable Pulling Load
Dynamic =Dynamic Load
EQX = Earthquake in X-direction
EQZ = Earthquake in Z-direction
WLX = Wind Load in X-direction
WLZ = Wind Load in Z-direction
- Dead Load =Self Weight Cable Weight +Termination Equipment Weight +Clamp Weight +Link Box Weight +Earth Strip Weight. Etc.
- Cable Pulling Load (Tension Load)-
Applicable for 1 cable at a time
Tension Load = L*W*f
Where,
L = Length of wire
W = Weight of cable
f = Co-efficient of friction
- Dynamic Load
FS= 2*10^-7*IS^2/A
IS= K*(SQRT2)*IC
Wat about the short circuit force ..
LikeLiked by 1 person
Dear Amit
Short Circuit Force is basically the force between two conductor or Two Cable .It is calculated as per IS/ IEC formula (Electrical Code) .
Regards
Satyajeet